
8 BRIGGSandSTRATTON.COM
Wiring Interconnections
All wiring must be the proper size, properly supported and
protected by conduit.
Complete the following connections between the transfer
switch, main distribution panel, utility power and generator,
as shown on the next page.
WARNING
Low voltage wire cannot be installed in same
conduit as power voltage wiring.
Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
•
High Voltage Wiring
1. Ensure utility power is turned OFF. Connect utility
feeder conductors to transfer switch terminals marked
“UTILITY CONNECTION”. Connect utility live to “N1”
and utility neutral to “N2”.
2. Connect distribution panel feeder conductors to transfer
switch terminals marked “LOAD CONNECTION”.
Connect live to “T1” and neutral to “T2”.
3. Connect distribution panel Ground conductor to the
transfer switch “GND” terminal.
NOTE: Assure grounding electrode conductor is connected
and bonded per applicable federal, state and local codes,
standards and regulations.
Generator feeder conductors are shown below:
4. Connect generator feeder conductor from the generator
circuit breaker terminal “E1” to transfer switch terminal
marked “GENERATOR CONNECTION” terminal “E1”
(see diagram at top of next column). This conductor
should pass through hole of current transformer before
making the connection.
5. Connect other generator feeder conductor from the
generator circuit breaker terminal “E2” to transfer
switch terminal marked “NEUTRAL”. This conductor
should pass through hole of current transformer before
making the connection.
6. Connect a cable from transfer switch terminal
marked “Neutral” to transfer switch terminal marked
“GENERATOR CONNECTION” terminal “E2”.
7. Connect a cable from transfer switch terminal marked
“Neutral” to transfer switch terminal marked “Ground”.
NOTE: This connection grounds the neutral side of the
generator output, and is required for correct operation of
protection devices in the installation.
8. Plug in current transformer leads into “CT1” and “CT2”
on control module.
9. Connect generator Ground conductor from the control
panel to the transfer switch “GND” terminal.
NOTE: Assure generator equipment grounding conductor
is connected per applicable federal, state and local codes,
standards and regulations.
10. Connect generator “UTILITY 230 VAC” terminals to
transfer switch “UTILITY 230 VAC” terminals (F1, F2).
Use minimum 2.5mm
2
conductors.
NOTE: Replace with fuse of same type and rating, 600 volt,
2 amp.
11. Tighten all wire connections/fasteners to proper torque
as shown below.
Low Voltage Wiring
1. Using 1.0mm
2
twisted pair conductors, no greater than
60 m in length, connect Tx Rx and Tx Rx Ground from
the generator control panel to the GND and T/R on the
transfer switch control board.
2. Tighten all wire connections/fasteners to proper torque
as shown on next page.
#22
E1
E2
Generator
Transfer
Switch
Komentarze do niniejszej Instrukcji