Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a
field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with
the location of these connections.
System Connectors
A
- Two Pin Terminal Block — Used to connect utility
240 VAC from fuse block in ATS to the control board.
Connect only one wire per terminal.
B
- Fault Contacts — Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
fault condition.
C
Transfer Switch Communication (TxRx and TxRx
GND)Connect to transfer switch control board for
communication interface using 18AWG twisted pair
wire.
D
+LED and GND ConnectionNot required for wireless
monitor included with unit. Available for optional
hardwired remote system status panel accessory,
#6154.
E
- Eight Pin Terminal Block — Used to connect signal
wires to the control board. Connect only one wire per
terminal.
F
- Power Connection (Line 1 and Line 2) — Power
connection to transfer switch.
G
- Neutral and Ground Connection — Connect to transfer
switch neutral and ground
For power output connection (Line 1, Line 2, Neutral, and Ground), refer to the following table:
Power output connections
minimum 300V, 75°C
15 kW 17 kW 20 kW
6AWG Copper 4AWG Copper 4AWG Copper
4AWG Aluminum 3AWG Aluminum 2AWG Aluminum
• Reference NEC 2011 table 310.15 (B) (16) • Use National Electric Code for correction factors and wire size calculations.
For utility circuit connection (Utility A and Utility B) use #14 AWG minimum 300 volt wire.
For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt wire.
When connecting to the terminal block, fasten only one wire to each connector screw.
Torque terminal block screws to 4.4 in-lb (0.49 Newton meter).
Torque circuit breaker connections to 45 in-lb (5 Newton meter).